3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The
setting is not applicable to this module.
NOTE
3
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is protected
by surge suppression devices.
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrange-
ment of these pins, see the Rear terminal assignments section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3–35: TYPICAL PIN INTERCONNECTION BETWEEN TWO G.703 INTERFACES
Pin nomenclature may differ from one manufacturer to another. Therefore, it is not uncommon to see pin-
outs numbered TxA, TxB, RxA and RxB. In such cases, it can be assumed that "A" is equivalent to "+" and
NOTE
"B" is equivalent to "–".
b) G.703 SELECTION SWITCH PROCEDURES
1.
Remove the G.703 module (7R or 7S). The ejector/inserter clips located at the top and at the bottom of each module,
must be pulled simultaneously in order to release the module for removal. Before performing this action, control
power must be removed from the relay. The original location of the module should be recorded to help ensure that
the same or replacement module is inserted into the correct slot.
3-32
Observing any fiber transmitter output can injure the eye.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
Figure 3–34: G.703 INTERFACE CONFIGURATION
X
1a
Shld.
X
1b
Tx -
G.703
X
2a
Rx -
CHANNEL 1
X
2b
Tx +
3a
X
Rx +
X
3b
SURGE
6a
Shld.
X
X
6b
Tx -
G.703
7a
Rx -
X
CHANNEL 2
X
7b
Tx +
8a
Rx +
X
X
8b
SURGE
B30 Bus Differential System
SETTINGS
PRODUCT SETUP
X
1a
Shield
X
1b
Tx –
G.703
X
2a
Rx –
channel 1
X
2b
Tx +
3a
X
Rx +
Surge
X
3b
X
6a
Shield
X
6b
Tx –
G.703
X
7a
Rx –
channel 2
X
7b
Tx +
X
8a
Rx +
Surge
X
8b
842773A2.CDR
X
1a
Shld.
X
1b
Tx -
X
2a
Rx -
X
2b
Tx +
3a
X
Rx +
X
3b
6a
X
Shld.
X
6b
Tx -
7a
X
Rx -
X
7b
Tx +
8a
X
Rx +
X
8b
3 HARDWARE
3.3.4 G.703 INTERFACE


DIRECT I/O
DIRECT I/O DATA RATE
G.703
CHANNEL 1
SURGE
G.703
CHANNEL 2
SURGE
831727A3.CDR
GE Multilin