6-2. Applied Control for Outdoor Unit

The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are available by setting relevant switches provided on the interface P.C.
board of the outdoor unit.

6-2-1. Outdoor Fan High Static Pressure Shift

Purpose/characteristics

This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example, unit
installation on the floor by floor installation.)
Setup
Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.
This function must be enabled with every discharge duct connected outdoor unit for both of the header and follower
units.
Specification
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a maximum
external static pressure not greater than specified in the table below. If a discharge duct with a resistance greater
than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static pressures of single units
are shown below (Table 1). In the case of combined use of multiple outdoor units, set all the units to the same
maximum external static pressure as the one with the lowest maximum external static pressure (see table2).
Table 1: Maximum External Static Pressures of Single Outdoor Units
Model
MMY- MAP0806* MAP1006* MAP1206* MAP14B6* MAP10A6*
Maximum external static pressure (Pa)
(*) Outdoor unit air flow
(m3/h)
(*) Calculate duct resistance from outdoor unit air flow.
Table 2: Maximum External Static Pressures for Combined Use of Single Units
(1-1) For HT8P,HT7P,HT8P-E,T8P-E,HT8P-TR model
Combined
horsepower output
8
10
12
14
16
18
20
22
24
26
28
30
32
Standard
34
models
36
38
40
42
44
46
48
50
52
54
56
58
60
20
22
36
High efficiency
38
models
40
42
44
54
60
60
50
40
9700
9700
12200
12200
Model
MMY-
Unit1
MAP0806*
MAP0806*
MAP1006*
MAP1006*
MAP1206*
MAP1206*
MAP1406*
MAP1406*
MAP1606*
MAP1606*
MAP1806*
MAP1806*
MAP2006*
MAP2006*
MAP2206*
MAP2206*
AP2416*
MAP1206*
AP2616*
MAP1406*
AP2816*
MAP1606*
AP3016*
MAP1606*
AP3216*
MAP1606*
AP3416*
MAP1806*
AP3616*
MAP2006*
AP3816*
MAP2206*
AP4016*
MAP2006*
AP4216*
MAP2206*
AP4416*
MAP2206*
AP4616*
MAP1606*
AP4816*
MAP1606*
AP5016*
MAP1806*
AP5216*
MAP2006*
AP5416*
MAP2206*
AP5616*
MAP2006*
AP5816*
MAP2206*
AP6016*
MAP2206*
AP2026*
MAP1006*
AP2226*
MAP1206*
AP3626*
MAP1206*
AP3826*
MAP1406*
AP4026*
MAP1406*
AP4226*
MAP1406*
AP4426*
MAP1606*
AP5426*
MAP2006*
MAP12A6*
MAP1406*
MAP1608*
50
50
50
40
12200
12200
12200
12600
Combination of outdoor units
Unit2
Unit3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
MAP1206*
-
MAP1206*
-
MAP1206*
-
MAP1406*
-
MAP1606*
-
MAP1606*
-
MAP1606*
-
MAP1606*
-
MAP2006*
-
MAP2006*
-
MAP2206*
-
MAP1606*
MAP1406*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP2006*
MAP1606*
MAP2006*
MAP1606*
MAP2206*
MAP1606*
MAP1006*
-
MAP1006*
-
MAP1206*
MAP1206*
MAP1206*
MAP1206*
MAP1406*
MAP1206*
MAP1406*
MAP1406*
MAP1406*
MAP1406*
MAP2006*
MAP1406*
− 92 −
MAP18B6*
MAP14A6* MAP16A6*
MAP1806*
40
50
50
50
12600
17300
17300
17300
Maximum external
static pressure
(Pa)
60
60
50
50
40
50
40
40
50
50
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
60
50
50
50
50
50
40
40
MAP2006*
MAP2206*
40
40
17900
18500