Toshiba MMY-MAP0806HT8P Service Manual page 176

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
A3-IPDU
Fan-IPDU
1
2
1
01
02
03
08
09
E31
E31
0A
0B
80
F01
F02
F03
F04
F04
F05
F05
01: TE1 sensor error
F06
F06
02: TE2 sensor error
01: TL1 sensor error
02: TL2 sensor error
F07
F07
03: TL3 sensor error
Location
of
detection
I/F
A3-IPDU
Fan-IPDU
2
1
2
1
2
10
11
12
13
18
19
1A
1B
Circle (O): Faulty IPDU
Indoor
unit
Indoor
unit
Indoor
unit
I/F
I/F
I/F
I/F
System
Description
status
IPDU
All stop
Communication is disrupted
communication
between IPDUs (P.C.
error
boards) in inverter box.
Communication
Communication between
All stop
MCU and Sub MCU stopped.
error between
MCU and Sub
MCU
Indoor TCJ
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
Indoor TC2
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
Indoor TC1
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
TD1 sensor
All stop
Sensor resistance is infinity
error
or zero (open/short circuit).
TD2 sensor
All stop
Sensor resistance is infinity
error
or zero (open/short circuit).
TE1/TE2
All stop
Sensor resistance is infinity
sensor error
or zero (open/short circuit).
TL1/TL2/TL3
All stop
Sensor resistance is infinity
sensor error
or zero (open/short circuit).
− 175 −
Error detection
Check items (locations)
condition(s)
• Check wiring and
connectors involved in
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
• Check for defect in outdoor
P.C. board (I/F, A3-IPDU
or Fan IPDU).
• Check for external noise.
• Operation of power supply
reset (OFF for 60 seconds
or more)
• Outdoor I/F PC board error
check
• Check connection of TCJ
sensor connector and
wiring.
• Check resistance
characteristics of TCJ
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC2
sensor connector and
wiring.
• Check resistance
characteristics of TC2
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TL1/
TL2/TL3 sensor connector.
• Check resistance
characteristics of TL1/TL2/
TL3 sensor.
• Check for defect in outdoor
P.C. board (I/F).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map1006ht8pMmy-map1806ht8pMmy-map2006ht8pMmy-map2206ht8pMmy-map1206ht8pMmy-map0806ht8jp ... Show all

Table of Contents