Toshiba MMY-MAP0806HT8P Service Manual page 115

Table of Contents

Advertisement

(Example)
System wiring
diagram
Address setting procedure 2
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system
(refrigerant line) or a "Digital Inverter" side.
Interface P.C. board on the header outdoor unit
Line address switches on the outdoor interface PC board ( : switch on, : switch off)
Line
SW13
address
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Controlling 2 or more refrigerant lines as a group
Outdoor
Indoor
Indoor
(Group control)
Remote
controller
SW06
SW07
1 2 3 4
1 2 3 4
SW11
SW12
1 2 3 4
1 2 3 4
SW14
3
4
1
2
3
×
×
×
×
×
×
×
O
×
×
×
O
×
×
O
O
×
×
×
O
×
×
O
O
×
×
O
O
×
O
O
O
×
×
×
×
×
×
×
O
×
×
×
O
×
×
O
O
×
×
×
O
×
×
O
O
Not used for setup of line address (do not change setup.)
Outdoor
Indoor
Indoor
SW09
SW10
1 2 3 4
1 2 3 4
SW13
SW14
1 2 3 4
1 2 3 4
Line
SW13
address
4
1
2
×
15
×
16
×
17
×
18
×
19
×
20
×
21
×
22
23
O
24
O
25
O
26
O
27
O
28
O
− 114 −
SW14
3
4
1
2
3
×
×
O
O
×
O
O
O
×
×
×
O
×
×
O
O
×
×
O
O
×
O
O
O
×
×
O
O
×
O
O
O
×
O
O
O
O
O
O
O
×
×
×
O
×
×
O
O
×
×
O
O
×
O
O
O
4
O
O
×
×
×
×
×
×
×
×
O
O
O
O

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map1006ht8pMmy-map1806ht8pMmy-map2006ht8pMmy-map2206ht8pMmy-map1206ht8pMmy-map0806ht8jp ... Show all

Table of Contents