Check codes Detected by TCC-LINK Central Control Device
Check code
Outdoor 7-segment display
Main
remote
Sub-code
controller
C
0
5
C
0
6
C
1
2
Differs according to
nature of alarm-causing
error
P30
(L20 displayed.)
Location
of
Description
System status
detection
TCC-LINK TCC-LINK
Continued
central control
operation
device
transmission
error
TCC-LINK
Continued
central control
operation
device reception
error
Batch alarm
General-
Continued
purpose
for general-
operation
device
purpose device
I/F
control interface
TCC-LINK Group control
Continued
follower unit
operation
error
Duplicated
Continued
central control
operation
address
− 186 −
Error detection
Check items (locations)
condition(s)
Central control device is
• Check for defect in central
unable to transmit signal.
control device.
• Check for defect in central
control communication
line.
• Check termination
resistance setting.
Central control device is
• Check for defect in central
unable to receive signal.
control device.
• Check for defect in central
control communication
line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check defect in P.C.
boards of devices at other
end of central control
communication line.
Error signal is input to control
• Check error input.
interface for general-purpose
devices.
Error occurs in follower unit
• Check check code of unit
under group control.
that has generated alarm.
([P30] is displayed on central
control remote controller.)
There is duplication in central
• Check address settings.
control addresses.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map1006ht8pMmy-map1806ht8pMmy-map2006ht8pMmy-map2206ht8pMmy-map1206ht8pMmy-map0806ht8jp ... Show all