Fan Operation Check In Outdoor Unit - Toshiba MMY-MAP0806HT8P Service Manual

Table of Contents

Advertisement

7-7-8. Fan Operation Check in Outdoor Unit

This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)
Do not use this function during operation of the compressor. It may damage the compressor.
Two fans move synchronously in two fan model (MMY-MAP1806* to MAP2206*).
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
SW02 SW03 7-segment display [B]
1
[ 63 ]
2
[ 62 ]
3
[ 61 ]
4
[ 60 ]
5
[ 59 ]
6
[ 58 ]
7
[ 57 ]
8
[ 56 ]
4
9
[ 55 ]
10
[ 54 ]
11
[ 53 ]
12
[ 52 ]
13
[ 51 ]
14
[ 50 ]
15
[ 49 ]
16
[ 48 ]
1
[ 47 ]
2
[ 46 ]
3
[ 45 ]
4
[ 44 ]
5
[ 43 ]
6
[ 42 ]
7
[ 41 ]
8
[ 40 ]
5
9
[ 39 ]
10
[ 38 ]
11
[ 37 ]
12
[ 36 ]
13
[ 35 ]
14
[ 34 ]
15
[ 33 ]
16
[ 32 ]
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
Fan mode
SW02 SW03 7-segment display [B]
63
1
62
2
61
3
60
4
59
5
58
6
57
7
56
8
55
9
54
10
53
11
52
12
51
13
50
14
49
15
48
16
47
1
46
2
45
3
44
4
43
5
42
6
41
7
40
8
39
9
38
10
37
11
36
12
35
13
34
14
33
15
32
16
− 149 −
[ 31 ]
[ 30 ]
[ 29 ]
[ 28 ]
[ 27 ]
[ 26 ]
[ 25 ]
[ 24 ]
6
[ 23 ]
[ 22 ]
[ 21 ]
[ 20 ]
[ 19 ]
[ 18 ]
[ 17 ]
[ 16 ]
[ 15 ]
[ 14 ]
[ 13 ]
[ 12 ]
[ 11 ]
[ 10 ]
[
9 ]
[
8 ]
7
[
7 ]
[
6 ]
[
5 ]
[
4 ]
[
3 ]
[
2 ]
[
1 ]
[
0 ]
Fan mode
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map1006ht8pMmy-map1806ht8pMmy-map2006ht8pMmy-map2206ht8pMmy-map1206ht8pMmy-map0806ht8jp ... Show all

Table of Contents