7-5. Troubleshooting in Test Operation

If there are phenomena such as the output of a check code or the remote controller is not accepted when powered-
on after wiring work or during address setup operation, the following causes are considered.

7-5-1. A Check Code is Displayed on the Remote Controller

Check the code
Header
displayed on the
unit 7-
indoor remote
segment
controller
display
L08
E08
Alternate
blinking
E04
E07
E06
E16
E16
Alternate
blinking
E23
E23
E25
E25
E26
E26
Alternate
blinking
L04
L04
L05(*)
L06
L06(*)
L08
L08
* "L05": Displayed on the indoor unit set up with priority
"L06": Displayed on the indoor units except the one set up with priority
C
W
h
e
n
o
u
d t
o
r o
p
o
w
r e
s i
Address setup error
• Only line addresses of the connected indoor units
are undefined.
• The outdoor line address and the line addresses
of all the indoor units do not match.
• The indoor addresses are duplicated. (Units
except those displaying E04 are duplicated.)
• A header unit is not set up in group control (except
groups displaying E04).
-XX
Duplication of indoor addresses (address number in
the subcode of the check code are duplicated).
There is no outdoor terminator resistor or
there are two or more terminator resistor.
(After address setup, when terminator
resistor setup is changed after powering-on)
Transmission circuit error at the interface side (PC
board failure)
After address setup, communication from all the
indoor units is interrupted under the condition that a
normal operation can be performed.
-XX
Exceeded the number or capacity of connected
indoor units
Communication between outdoor units has stopped. Check the number of connected outdoor units.
Duplication of outdoor addresses (only when an
outdoor address was manually set up)
Number of connected outdoor units has decreased.
• When installing an outdoor backup
-XX
• The power of a follower unit is not turned on.
Duplication of outdoor line addresses
• Line address setup error (occurred after
connection between U1/U2 and U3/U4
connectors)
Duplication of indoor units with priority
There are two or more indoor units set up with
priority.
Address setup error
• Only indoor addresses of all the connected indoor
units are undefined.
a
u
s
e
o
f f
C
Set up the address again.
Set up the address again.
Check SW30 bit 2 of the header unit.
ON
No connection between multiple refrigerant lines:
1
2
SW30 bit 2 is on.
Connection between multiple refrigerant lines:
SW30
SW30 bit 2 of the connected header unit is turned on
only for one line.
Replace the interface PC board.
Check and correct disconnection of the indoor/
outdoor communication line (the communication line
between the header unit and the leading indoor
unit).
Check for the influence of communication noise.
Adjust the number or capacity of connected indoor
units.
Check that outdoor unit power is on.
Do not use manual setup for outdoor addresses.
Correction of the cause of error occurrence
• If it occurs when installing a backup, clear the error
• If the power of a follower unit is not turned on, turn
Modify the line address setup of the header unit
between lines. (Set up SW13 and SW14 on the
interface PC board.)
Set up priority only for one indoor unit.
Among indoor units indicating "L05," set one unit
with priority.
Set up the addresses again.
Modify the setup.
− 127 −
C
o
u
t n
r e
m
e
a
s
u
h
e
k c
h t
t a
h t
e
h
e
a
d
r e
o
u
d t
o
r o
after setup finishes.
on the power.
e r
s
u
n
t i
p
o
w
r e
s i
o
n