6-2. Applied Control for Outdoor Unit

The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are available by setting relevant switches provided on the interface P.C.
board of the outdoor unit.

6-2-1. Outdoor Fan High Static Pressure Shift

Purpose/characteristics
This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example, unit
installation on the floor by floor installation.)
Setup
Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.
This function must be enabled with every discharge duct connected outdoor unit for both of the header and follower
units.
Specification
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a maximum
external static pressure not greater than specified in the table below. If a discharge duct with a resistance greater
than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static pressures of single units
are shown below (Table 1). In the case of combined use of multiple outdoor units, set all the units to the same
maximum external static pressure as the one with the lowest maximum external static pressure (see table2).
Table 1: Maximum External Static Pressures of Single Outdoor Units
Model
Maximum external static pressure
(*) Outdoor nuit air flow
(*) Calculate duct resistance from outdoor unit air flow.
Table 2: Maximum External Static Pressures for Combined Use of Single Units
(1-1) Standard models
Combined
horsepower output
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
AMP Air Conditioning
MMY-
MAP0806*
MAP1006*
(Pa)
60
60
(m3/h)
9700
9700
Combination of outdoor units
Model
MMY-
Unit 1
MAP0806*
MAP0806*
MAP1006*
MAP1006*
MAP1206*
MAP1206*
MAP1406*
MAP1406*
MAP1606*
MAP1606*
MAP1806*
MAP1806*
MAP2006*
MAP2006*
MAP2206*
MAP2206*
AP2416*
MAP1206*
MAP1206*
AP2616*
MAP1406*
MAP1206*
AP2816*
MAP1606*
MAP1206*
AP3016*
MAP1606*
MAP1406*
AP3216*
MAP1606*
MAP1606*
AP3416*
MAP1806*
MAP1606*
AP3616*
MAP2006*
MAP1606*
AP3816*
MAP2206*
MAP1606*
AP4016*
MAP2006*
MAP2006*
AP4216*
MAP2206*
MAP2006*
AP4416*
MAP2206*
MAP2206*
AP4616*
MAP1606*
MAP1606*
AP4816*
MAP1606*
MAP1606*
AP5016*
MAP1806*
MAP1606*
AP5216*
MAP2006*
MAP1606*
AP5416*
MAP2206*
MAP1606*
AP5616*
MAP2006*
MAP2006*
AP5816*
MAP2206*
MAP2006*
AP6016*
MAP2206*
MAP2206*
MAP1206* MAP14B6* MAP1406*
MAP1606* MAP18B6* MAP1806*
50
40
50
12200
12200
12200
Maximum external
static pressure
Unit 2
Unit 3
MAP1406*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
MAP1606*
− 91 −
MAP2006*
40
40
50
40
12600
17300
17300
17900
(Pa)
60
60
50
50
40
50
40
40
50
50
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40