6-2-6. Snowfall Fan Control

Header outdoor unit
SW1: Snowfall detection switch (snowfall sensor)
Operation
An external snowfall signal turns on the outdoor unit fan.
Terminal
Input signal
ON
OFF
COOL
(SW1)
ON
OFF
The input signal is recognized during its rising/falling phase.
(After reaching the top/bottom of the rising/falling edge, the signal must remain there for at least 100 ms.)
The optional P.C. board should be connected to the header outdoor unit (U1).

6-2-7. External master ON/OFF Control

SW1: Operation input switch
SW2: Stop input switch
Operation
The system is started/stopped from the outdoor unit.
Terminal
Input signal
ON
COOL
(SW1)
OFF
ON
HEAT
(SW2)
OFF
The input signal is recognized during its falling phase. (After reaching the bottom of the falling edge, the signal must
remain there for at least 100 ms.)
CAUTION
(1) Do not turn on the COOL (SW1) and HEAT (SW2) terminals simultaneously.
(2) Be sure to provide a contact for each terminal.
External signal: No-voltage pulse contact
The optional P.C. board should be connected to the header outdoor unit (U1).
Connection
Outdoor unit
cable
interface PCB
C
N
5
0
9
Operation
All indoor units
operate together
All indoor units
operate together
Header outdoor unit
Connection
Outdoor unit
cable
interface PCB
C
N
5
1
2
Operation
Turns on all indoor
units
Turns off all indoor
units
Locally procured
Optional PCB
TB1
COM
COOL
P
J
1
7
Shield
HEAT
wire
Locally procured
Optional PCB
TB1
COM
P
J
1
7
COOL
HEAT
Shield
wire
− 100 −
Snowfall sensor
SW1
SW1
SW2