13-1-5. Comp-IPDU
<MAP10A6∗, 12A6∗, 1406∗, 1606∗, 18B6∗ type>
This board is commonly installed in different models before shipment. Set the DIP switch (SW800) setting of the
service board to the switch setting before replacement.
Replacement Steps:
(1) Turn off the power supply of the outdoor unit and allow at least 3 minutes for the capacitor to discharge.
(2)Remove all the connectors and the Faston and screw terminals(①) connected to the Compressor IPDU.
(Remove the connectors by pulling the connector body. Do not pull the wire).
(3)Remove all the four screws(②) which secures the Compressor IPDU to the Heat sink.
(These screws are to be re-used after procedure.)
(4)Remove the Compressor IPDU from the four spacers (③) by pinching the top of the spacers by round-nose pliers.