4-6. Emergency Operation (Heating Operation under
Header Outdoor Unit Backup Scenario)
Header unit (MMY-MAP1606HT*)
Leakage form PMV:
Liquid-side service valve
= Full closure
PMV1
PMV3
TE1
TL1
TE2
TL2
TS3
FP
SV3D
Fusible
Oil
Plug
Separator
SV
Liquid tank
SV41
SV
TD1
Sub cool
heat exchanger
圧縮機
(インバータ)
Compressor
1
PMV4
TK1
TL3
Check joint
Balance pipe service valve
= Full opening
Gas-side service valve
= Full closure
TC2 TCJ
Heating
Trouble header outdoor unit
ON
4-Way valve
SV3A
ON
SV4(n)
SV3B
OFF
SV52
SV3C
Close
PMV1
SV3D
Close
PMV3
Outdoor fan
Close
PMV4
(*1) SV4 (n) of stopped compressor (n)=ON
(*2) It may be controlled.
The outdoor unit which communication line between indoor and outdoor is connected is the "Header unit".
Other outdoor units are called "Follower units".
Trouble
Fan
M
Fan motor
Right side
TO
Main heat exchanger
Right side Sub heat exchanger
TG1
Left side
TG2
Main heat exchanger
Left side Sub heat exchanger
4-Way valve
TS1
Check Joint
Pressure sensor
(high pressure)
SV2
Accumulator
SV
SV42
SV3C
SV
TD2
TK4
HPS
HPS
Compressor
2
TK2
Oil
TK5
Header
SV3A
SV
SV3B
TC1
TC2
TCJ
Temporal header outdoor unit
OFF
4-Way valve
ON
OFF(*1)
SV4(n)
OFF
SV52
OFF
Control
PMV1
OFF
Control Outdoor fan Control
PMV3
Close(*2)
PMV4
High-pressure gas refrigerant
Condensed liquid refrigerant
( 28 HP system described in the example of (16 HP + 12 HP))
Follower unit (MMY-MAP1206HT*)
PMV1
TL1
Check
Joint
Pressure sensor
TS3
(low pressure)
FP
Fusible
Plug
Liquid tank
Sub cool
heat exchanger
PMV4
TL3
Check joint
TC1
TC2 TCJ
Heating
ON
Control
SV3A
Control
SV3B
OFF
Control
SV3C
Control
SV3D
Evaporative gas refrigerant (Low pressure)
Low-pressure circuit (Refrigerant recovery line)
− 66 −
Set Up as Temporary
Header Unit during
Emergency Operation
M
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
TE1
SV
SV52
Check Joint
Pressure sensor
(high pressure)
SV2
SV3D
SV
Oil
Separator
SV
SV41
SV42
SV3C
SV
TD1
TD2
TK4
HPS
HPS
圧縮機
(インバータ)
Compressor
Compressor
1
2
TK1
TK2
Oil
TK5
Header
SV3A
SV
SV3B
TC1
TC2 TCJ
Heating
Fan
TO
4-Way valve
Check
Joint
TS1
Pressure sensor
(low pressure)
Accumulator
SV
TC1
Heating