7-3-4. Snowfall fan control

Operation
An external snowfall signal turns on the outdoor unit fan.
Terminal
COOL
(SW1)
The input signal is recognized during its rising / falling phase.
(After reaching the top / bottom of the rising / falling edge, the signal must remain there for at least 100 ms.)

7-3-5. External master ON / OFF control

Operation
The system is started / stopped from the outdoor unit.
Terminal
COOL
(SW1)
HEAT
(SW2)
The input signal is recognized during its falling phase. (After reaching the bottom of the falling edge, the signal must
remain there for at least 100 ms.)
CAUTION
(1) Do not turn on the COOL (SW1) and HEAT (SW2) terminals simultaneously.
(2) Be sure to provide a contact for each terminal.
External signal: No-voltage pulse contact
AMP Air Conditioning
Outdoor unit
Connection
Outdoor unit
cable
interface PCB
C
N
5
0
9
SW1: Snowfall detection switch (snowfall sensor)
Input signal
Operation
Snowfall fan control
ON
(Turns on outdoor
OFF
unit fan)
Normal operation
ON
(Cancels control)
OFF
Outdoor unit
Connection
Outdoor unit
cable
interface PCB
C
N
5
1
2
SW1: Operation input switch
SW2: Stop input switch
Input signal
Operation
Turns on all indoor
ON
units
OFF
Turns off all indoor
ON
units
OFF
Locally procured
Optional PCB
TB1
COM
COOL
P
J
1
7
HEAT
Shield
wire
Locally procured
Optional PCB
TB1
COM
COOL
P
J
1
7
HEAT
Shield
wire
42
58
www.ampair.co.uk | sales@ampair.co.uk
Snowfall sensor
SW1
SW1
SW2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents