6

Basic parameters (Menu 0)

Menu 0 is used to bring together various commonly used parameters for basic easy set up of the
drive. All the parameters in Menu 0 appear in other menus in the drive. Menus 22 can be used to
configure the parameters in Menu 0.
6.1

Menu 0: Basic parameters

Parameter
Minimum Reference
00.001
Clamp
Maximum
00.002
Reference Clamp
00.003 Acceleration Rate 1
00.004 Deceleration Rate 1
00.005 Drive Configuration
00.006 Motor Rated Current
00.007 Motor Rated Speed
00.008 Motor Rated Voltage
Motor Rated Power
00.009
Factor
00.010 User Security Status
00.015 Jog Reference
Analog Input 1
00.016
Mode
Bipolar Reference
00.017
Enable
00.018 Preset Reference 1
00.025 User Security Code
Power-up Keypad
00.027
Control Mode
Reference
00.028 Ramp Mode Select
00.030 Parameter Cloning
00.031 Stop Mode
Dynamic V to F
00.032
Select
Catch A Spinning
00.033
Motor
Digital Output 1
00.035
Control
Maximum Switching
00.037
Frequency
Unidrive M100-101 Quick Start Guide
Issue Number: 6
Range ( )
OL
±VM_NEGATIVE_REF_CLAMP 1 Hz
±VM_POSITIVE_REF_CLAMP Hz
±VM_ACCEL_RATE s
±VM_ACCEL_RATE s
AV (0), AI (1), AV.Pr (2), AI.Pr (3),
Preset (4), Pad (5), Pad.Ref (6),
torque (8)
0.00 to VM_RATED_CURRENT A
0.0 to 80000.0 rpm
0 to VM_AC_VOLTAGE_SET V
0.00 to 1.00
LEVEL.0 (0), ALL (1), r.only.0 (2),
r.only.A (3), Status (4), no.acc(5)
0.00 to 300.00 Hz
4-20.S (-6), 20-4.S (-5), 4-20.L (-4),
20-4.L (-3), 4-20.H (-2), 20-4.H (-1),
0-20 (0), 20-0 (1), 4-20.tr (2), 20-4.tr (3),
4-20 (4), 20-4 (5), Volt (6)
Off (0) or On (1)
±VM_SPEED_FREQ_REF Hz
0 to 9999
Reset (0), Last (1), Preset (2)
Fast (0), Std (1), Std.bst (2), Fst.bst (3)
None (0), rEAd (1), Prog (2), Auto (3),
boot (4)
Coast (0), rp (1), rp.dc I (2), dc I (3),
td.dc I (4),dis (5), No.rp (6)
0 to 1
dis (0), Enable (1), Fr.Only (2),
Rv.Only (3)
0 to 21
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6), 12 (7), 16 (8) kHz
Default ( )
OL
0.00 Hz
RW Num
50 Hz default: 50.00 Hz
RW Num
60 Hz default: 60.00 Hz
5.0 s
RW Num
10.0 s
RW Num
*
AV (0)
RW
Maximum Heavy Duty
RW Num
Rating (11.032) A
50 Hz default:
1500.0 rpm
RW Num
60 Hz default:
1800.0 rpm
110 V drive: 230 V
200 V drive: 230 V
RW Num
400 V drive 50 Hz: 400 V
400 V drive 60 Hz: 460 V
0.85
RW Num
LEVEL.0 (0)
RW Num ND NC PT
1.50 Hz
RW Num
Volt (6)
RW
Off (0)
RW
0.00 Hz
RW Num
0
RW Num ND NC PT US
Reset (0)
RW
Std (1)
RW
None (0)
RW
rp (1)
RW
0
RW Num
dis (0)
RW
0
RW
3 (3) kHz
RW
Type
US
US
US
US
Txt
PT US
RA
US
US
RA
US
RA
US
US
Txt
US
Bit
US
US
Txt
US
Txt
US
Txt
NC
US
Txt
US
US
Txt
US
US
Txt
US
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m100

Table of Contents