Figure 4-13 Pr 00.005 = Torque (50 Hz)
10k
Figure 4-14 Pr 00.005 = Torque (60 Hz)
10k
4.5

EMC

4.5.1
Internal EMC filter
It is recommended that the internal EMC filter be kept in place unless there is a specific reason for
removing it. If the drive is used as a motoring drive as part of a regen system, then the internal EMC
filter must be removed.
The internal EMC filter reduces radio-frequency emission into the line power supply.
For longer motor cables, the filter continues to provide a useful reduction in emission levels and
when used with any length of shielded motor cable up to the limit for the drive, it is unlikely that
nearby industrial equipment will be disturbed. It is recommended that the filter be used in all
applications unless the instructions given above require it to be removed, or where the ground
leakage current is unacceptable.
Unidrive M100-101 Quick Start Guide
Issue Number: 6
1
0 V
Torque reference
2
input (AI 1)
4
+ 10 V output
+ 24 V output
9
Digital output
10
WARNING
(zero frequency)
11
Drive enable
Run forward
12
Torque mode select
13
1
0 V
Torque reference
2
input (AI 1)
4
+ 10 V output
+ 24 V output
9
Digital output
10
(zero frequency)
WARNING
11
Not stop
12
Run
Torque mode
13
select
When torque mode is selected and the
drive is connected to an unloaded motor,
the motor speed may increase rapidly to
the maximum speed (Pr 00.002 +10 %)
When torque mode is selected and the
drive is connected to an unloaded motor,
the motor speed may increase rapidly to
the maximum speed (Pr 00.002 +10 %)
17