Section 3
Analog inputs
3.4
Table 8:
AISVBAS Non group settings (basic)
Name
Values (Range)
PhaseAngleRef
TRM40-Ch1 - Ch12
TRM41-Ch1 - Ch12
MU1-L1I
MU1-L2I
MU1-L3I
MU1-L4I
MU1-L1U
MU1-L2U
MU1-L3U
MU1-L4U
MU2-L1I
MU2-L2I
MU2-L3I
MU2-L4I
MU2-L1U
MU2-L2U
MU2-L3U
MU2-L4U
MU3-L1I
MU3-L2I
MU3-L3I
MU3-L4I
MU3-L1U
MU3-L2U
MU3-L3U
MU3-L4U
MU4-L1I - L4I
MU4-L1U - L4U
MU5-L1I - L4I
MU5-L1U - L4U
MU6-L1I - L4I
MU6-L1U - L4U
Table 9:
TRM_12I Non group settings (basic)
Name
CTStarPoint1
CTsec1
CTprim1
CTStarPoint2
CTsec2
CTprim2
CTStarPoint3
CTsec3
CTprim3
Table continues on next page
66

Settings

Dependent on ordered IED type.
Unit
-
Values (Range)
Unit
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
Step
-
Step
Default
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
1MRK502052-UEN B
Default
Description
TRM40-Ch1
Reference channel
for phase angle
presentation
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Technical manual