Settings - ABB REG670 Technical Manual

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 6
Differential protection
6.3.5
Table 56:
GENPDIF Group settings (basic)
Name
Operation
IdMin
IdUnre
OpNegSeqDiff
IMinNegSeq
148
Table 55:
GENPDIF Output signals
Name
TRIP
TRIPRES
TRIPUNRE
TRNSUNR
TRNSSENS
START
STL1
STL2
STL3
BLKH
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDNSMAG
IBIAS

Settings

Values (Range)
Unit
Off
-
On
0.05 - 1.00
IB
1.00 - 50.00
IB
Off
-
On
0.02 - 0.20
IB
Type
Description
BOOLEAN
General, common trip signal
BOOLEAN
Trip signal from restrained differential protection
BOOLEAN
Trip signal from unrestrained differential protection
BOOLEAN
Trip signal from unrestr. neg. seq. diff. protection
BOOLEAN
Trip signal from sensitive neg. seq. diff. protection
BOOLEAN
Common start signal from any phase
BOOLEAN
Start signal from phase L1
BOOLEAN
Start signal from phase L2
BOOLEAN
Start signal from phase L3
BOOLEAN
Common harmonic block signal
BOOLEAN
An open CT was detected
BOOLEAN
Open CT Alarm output signal. Issued after a
delay ...
REAL
Instantaneous differential current L1; in primary
Amperes
REAL
Instantaneous differential current L2; in primary
Amperes
REAL
Instantaneous differential current L3; in primary
Amperes
REAL
Negative Sequence Differential current; in primary
Amperes
REAL
Magnitude of the common Bias current; in primary
Amperes
Step
Default
-
Off
0.01
0.25
0.01
10.00
-
On
0.01
0.04
1MRK502052-UEN B
Description
Operation Off / On
Section 1 sensitivity, multiple of generator
rated current
Unrestr. prot. limit, multiple of generator
rated current
Negative Sequence Differential Enable
Off/On
Neg. sequence curr. limit, as multiple of
gen. rated curr.
Technical manual