Section 5
Local Human-Machine-Interface LHMI
92
signal is not present any more. If the signal is still present after acknowledgment it gets
a steady light.
Activating
signal
LED
Acknow.
IEC01000231 V1 EN
Figure 16:
Operating Sequence 3 LatchedAck-F-S
The sequence described below is valid only if the same function block
is used for all three colour LEDs.
When an acknowledgment is performed, all indications that appear before the
indication with higher priority has been reset, will be acknowledged, independent of
if the low priority indication appeared before or after acknowledgment. In figure
is shown the sequence when a signal of lower priority becomes activated after
acknowledgment has been performed on a higher priority signal. The low priority
signal will be shown as acknowledged when the high priority signal resets.
Activating
signal GREEN
Activating
signal RED
LED
Acknow
IEC09000313 V1 EN
Figure 17:
Operating Sequence 3 (LatchedAck-F-S), 2 colors involved
If all three signals are activated the order of priority is still maintained.
Acknowledgment of indications with higher priority will acknowledge also low
priority indications, which are not visible according to figure 18.
R
R
1MRK502052-UEN B
en01000231.vsd
G
IEC09000313_1_en.vsd
Technical manual
17