Figure 255:
Principle logic for Voltage differential function VDCPTOV
9.5.8
Technical manual
tAlarm
AND
t
AND
OR
t1
AND
t

Technical data

Table 297:
VDCPTOV technical data
Function
Voltage difference for alarm and
trip
Under voltage level
Independent time delay for
voltage differential alarm at 0.8 to
1.2 x UDAlarm
Independent time delay for
voltage differential trip at 0.8 to
1.2 x UDTrip
Independent time delay for
voltage differential reset at 1.2 to
0.8 x UDTrip
AND
O
AND
R
AND
AND
O
AND
R
AND
Range or value
(2.0–100.0) % of
UBase
(1.0–100.0) % of
UBase
(0.000–60.000)s
(0.000–60.000)s
(0.000–60.000)s
Section 9
Voltage protection
tReset
tTrip
t
t
AND
AND
tAlarm
t
AND
AND
AND
en06000382-2.vsd
Accuracy
±0.5% of U
r
±0.5% of U
r
±0.2% or ±40 ms whichever is
greater
±0.2% or ±40 ms whichever is
greater
±0.2% or ±40 ms whichever is
greater
TRIP
START
ALARM
U1LOW
U2LOW
531