Cross-Sensitivity Response Data; Table 1-7. Typical Chillgard Rt System For R-113 Cross-Sensitivity Response Data - MSA Chillgard RT Instruction Manual

Refrigerant monitor
Table of Contents

Advertisement

Table 1-7. Typical Chillgard RT System for
R-113 Cross-Sensitivity Response Data
GAS
R11
R12
R22
R123
R134A
R114
R113
TEST CONDITIONS:
Table 1-8. Typical Chillgard RT System for
R-113 Cross-Sensitivity Response Data
GAS
R11
R12
R22
R113
R123
R134a
R114
TEST CONDITIONS:
Table 1-9. Typical Chillgard RT System for
R-500 Cross-Sensitivity Response Data
GAS
R11
R22
R113
R114
R123
R134a
R502
R500
TEST CONDITIONS:
1-12
CONCENTRATION (PPM)
100
100
100
100
100
100
100
Calibrated 0-1000 PPM R-113 in N 2 ; Temperature: 25°C
CONCENTRATION (PPM)
100
100
100
100
100
100
100
Calibrated 0-1000 PPM R-114 in N 2 ; Temperature: 25°C
CONCENTRATION (PPM)
100
100
100
100
100
100
100
100
Calibrated 0-1000 PPM R-500 in N 2 ; Temperature: 25°C
EQUIVALENT PPM R-113
1
10
5
125
175
155
100
EQUIVALENT PPM R-114
105
50
35
30
3
20
100
EQUIVALENT PPM R-500
8
0
41
60
2
7
5
100

Hide quick links: