Ferrite Bead Installation; Caution - MSA Chillgard RT Instruction Manual

Refrigerant monitor
Table of Contents

Advertisement

Ferrite Bead Installation

Some models are shipped with ferrite beads. Follow the instructions
below for proper installation.
The input and output signals must be connected by using twisted,
shielded wire pairs.
The shield or its drain wire (FIGURE 2-6) must be connected to the
grounding terminal on the power supply plate.
Each unit is supplied with Thora-Electronik #16-28-9 or equivalent
ferrite (P/N 10017468).
The shield must also be connected to ground at the receiving
equipment.
The RS 485 communications lines to the relay module must be
wired in a similar manner. See Appendix B for more information on
the relay module.
Bundle low voltage wiring together (lower than 30 volts),
separate from high voltage wiring (higher than 30 volts).
Figure 2-6. Ferrite Bead Installation