Power Control Status
This screen is displayed only when Power Control is enabled (available from communication board (CPU)
firmware version 2.7xx/3.7xx and later).
P W R
C T R L :
P W R
L i m i t :
C o s P h i :
P o w e r
P r o d :
PWR CTRL: The power control status:
l
REMOTE - Communication with the RRCR or smart energy manager is confirmed/validated.
o
LOCAL - The power is controlled locally (e.g. by a fixed limit), or this inverter limits the PV power
o
production to its relative portion of the feed-in power limit, as a result of disconnected
communication with the smart energy manager. If this status appears, check the communication
to the smart energy manager or the communication to the meter.
PWR Limit: The inverter maximum output power set by one of the power limiting options:
l
RRCR
o
Smart energy manager (Feed-in limitation)
o
P(f)
o
P(U)
o
Q(U)
o
Cos Phi: The ratio between active to reactive power
l
Power Prod: The power produced by the inverter
l
For more information, refer to the Power Control Application Note, available on the
SolarEdge website at http://www.solaredge.us/files/pdfs/application_note_power_
control_configuration.pdf.
Battery Status
This screen is displayed only when the battery is configured, and shows the battery
identification information, its charging status and power, and the operating mode.
B S N :
X X X X X X X X X
S O E :
8 9 %
T o t a l :
S t a t e :
BSN: Battery serial number
l
ID: Battery identification - should be 24 as set up above
l
SOE: State of Energy - the battery capacity percentage (calculated as Available Energy\Max. Energy)
l
PWR: The charging or discharging power (in Watts) according to the battery state (see below)
l
Total: The total discharged energy in Watt/hour
l
State: The battery status: Charging/ Discharging, Idle, Init (pre-heating) or Fault <error code>.
l
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
R E M O T E
1 0 . 0 4
k W
0 . 9
7 0 0 0 W
I D : 2 4
W W W W
P W R :
2 W
< x > W h
C h a r g i n g
Chapter 7: User Interface