DIP-Switch Setup - Two Powerwall1 Batteries

DIP-Switch Setup - Two Powerwall1 Batteries
System Component
Batteries
Tesla Powerwall1 batteries Type B (Figure 56)
Tesla Powerwall1 batteries Type C, E
(Figure 57)
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
Communication and Termination Switches
Modbus protocol:
 
Single battery or the battery is the last in the chain
l
(termination):
S2, S6: Left
o
S1, S5: Down
o
S3, S4: UP
o
 
If the battery is not the last in the chain (no termination):
l
S2, S6: Left
o
S1, S5: Down
o
S3, S4: Down
o
Termination:
If the battery is not the last in the chain: Middle - No
o
termination
Single battery or the battery is the last in the
o
chain: Bottom - Termination (with bias)
Modbus protocol:
 
Right (RS485)
o
Address Switches
Battery 1 - located closest to the inverter (address ID 24):
Switch 1: Right
o
Switch 2: Right
o
Switch 3: Right
o
Battery 2 - at the end of chain (address ID 25) :
Switch 1: Left
o
Switch 2: Right
o
Switch 3: Right
o
Battery 1 - located closest to the inverter (address ID 24):
Switch 1: Right
o
Switch 2: Right
o
Switch 3: Right
o
Battery 2 - at the end of chain (address ID 25) :
Switch 1: Left
o
Switch 2: Right
o
Switch 3: Right
o
111