Appendix 3.1 Offgan - Mitsubishi Q64RD User Manual

Thermocouple input module melsec-q series
Hide thumbs Also See for Q64RD:
Table of Contents

Advertisement

APPENDIX

Appendix 3.1 OFFGAN

Internal device
Set data
(System, user)
Bit
(S)
[Instruction
[Execution
symbol]
condition]
G.OFFGAN
GP.OFFGAN
Device
Un
Start I/O number of the module
Mode switching
0: Switching to normal mode
(S)
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to
offset/gain setting mode".
App. - 4
Switches the mode of the Q64RD. (Normal mode to offset/gain setting mode,
offset/gain setting mode to normal mode)
MELSECNET/H
File
Direct J \
register
Word
Bit
Command
Command
Description
(1) Function
Switches the mode of the Q64RD.
• Normal mode to offset/gain setting mode
• Offset/gain setting mode to normal mode
POINT
When the offset/gain setting mode is switched to the normal mode, Module Ready
(X0) turns from OFF to ON.
Note that initial setting processing will be executed if there is a sequence program
that makes initial setting when Module Ready (X0) turns ON.
(2) Operation error
No errors.
Usable devices
Special
function
register
module
Word
U \G
G.OFFGAN
GP.OFFGAN
Set data
MELSEC-Q
Index
Constant
Z
K, H
S
Un
Un
Setting range
0 to FE
H
0 ,1
Other
(S)
(S)
Data type
Binary 16 bits
Binary 16 bits
App. - 4

Advertisement