5 UTILITY PACKAGE (GX Configurator-TI)

5.6.2 Offset/gain setting operation

5 - 18
Perform the offset/gain setting operation in the following sequence.
(1) Switch to the offset/gain setting mode
Change switch 4 for intelligent function module switch setting to the offset/gain
setting mode and switch 2 to the user setting. (Refer to Section 4.5)
(2) Switch to the offset/gain setting screen
Display the offset/gain setting screen using the operation described in Section
5.6.1.
(3) Adjustment of the offset and gain values
(a) Set the offset value
Enter the desired value into the Setting (value) field for CH.
Temperature Setting Value, and click the Execute test button.
(b) Determine the offset value
Select "Request" from the Setting (value) field for CH.
Request, and click the [Execute test] button. After making sure that the
offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF"
from the Setting (value) field for CH.
Execute test button.
(c) Set the gain value
Enter the desired value into the Setting (value) field for CH.
Temperature Setting Value, and click the Execute test button.
(d) Determine the gain value
Select "Request" from the Setting (value) field for CH.
Request, and click the [Execute test] button. After making sure that the
offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF"
from the Setting (value) field for CH.
Execute test button.
(e) To set the offset/gain for more than one channel, repeat steps (a) to (d).
(4) Write the offset/gain setting values to the module
Write the offset/gain settings to the module after completing the settings for all channels
using the user range setting. Note that if settings are written while offset/gain settings
are incomplete, the status at that point will be written to the module.
(a) Write to the Q64RD
Select "Request" from the Setting (value) field for User Range Write
Request, and click the Execute test button.
(b) Confirm execution of write and exit
After confirming that the indication of the Current value field for User Range
Write Status Signal changes from "Completed" to " Not Completed ", select
"OFF" from the Setting (value) field for User Range Write Request, and click
the Execute test button.
(c) Error handling
Confirm that the ERROR LED for the Q64RD is off. If the ERROR LED is lit,
click on Close , check the error code on the monitor screen, and then
perform the offset/gain settings again.
MELSEC-Q
Offset Setting
Offset Setting Request, and click the
Gain Setting
Gain Setting Request, and click the
Offset
Gain
5 - 18