I/O Signals For Programmable Controller Cpu; I/O Signal List - Mitsubishi QJ71MT91 User Manual

Modbus/tcp interface module melsec-q series
Hide thumbs Also See for QJ71MT91:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.2 I/O Signals for Programmable Controller CPU

3.2.1 I/O signal list

3
Signal Direction QJ71MT91
Device
No.
Module READY 1
X0
ON : Accessible
OFF: Inaccessible
Basic parameter setting, normally
completed
X1
ON : Normally completed
OFF:
Basic parameter setting, error completed
X2
ON : Error completed
OFF:
Basic parameter setting existence
X3
ON : Parameters set
OFF: No parameters set
Automatic communication parameter
setting, normally completed
X4
ON : Normally completed
OFF:
Automatic communication parameter
setting, error completed
X5
ON : Error completed
OFF:
Automatic communication operation status
X6
ON : Operating
OFF: Stopped
Automatic communication error status
X7
ON : Error occurred
OFF: No error
MODBUS
R
device assignment parameter
setting, normally completed
X8
ON : Normally completed
OFF:
MODBUS
device assignment parameter
R
setting, error completed
X9
ON : Error completed
OFF:
3 - 2
This section explains the I/O signals of the QJ71MT91 for the programmable controller
CPU.
The following table shows the I/O signals of the QJ71MT91.
The following I/O signal assignment is based on the case where the start I/O No. of the
QJ71MT91 is "0000" (installed to slot 0 of the main base unit).
Device X represents an input signal from the QJ71MT91 to the programmable
controller CPU.
Device Y shows an output signal from the programmable controller CPU to the
QJ71MT91.
Refer to the corresponding reference sections for details.
Programmable controller CPU
Reference
Signal name
1: Turns ON when the QJ71MT91 is ready after the programmable controller is turned ON
from OFF or after the programmable controller CPU is reset.
Signal Direction Programmable controller CPU
Device
section
No.
Section
Y0
Use prohibited
11.1
Basic parameter setting request
Y1
ON : Being requested
OFF: Not requested
Section
9.1.1
Y2
Use prohibited
Y3
Automatic communication parameter
setting request/automatic communication
start request
Y4
ON : Parameter setting being
requested/start being requested
OFF : No parameter setting requested/no
Section
start requested
5.2.1,
9.1.2
Y5
Use prohibited
Automatic communication stop request
Y6
ON : Being requested
OFF: Not requested
Section
Y7
Use prohibited
5.2.1
MODBUS
R
setting request
Y8
ON : Being requested
OFF: Not requested
Section
9.1.3
Y9
Use prohibited
MELSEC-Q
QJ71MT91
Signal name
device assignment parameter
(Continued on next page)
Reference
section
Section
9.1.1
Section
5.2.1,
9.1.2
Section
5.2.1
Section
9.1.3
3 - 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents