Mitsubishi QJ71MT91 User Manual page 85

Modbus/tcp interface module melsec-q series
Hide thumbs Also See for QJ71MT91:
Table of Contents

Advertisement

6 PRE-OPERATIONAL PROCEDURES AND SETTING
6 - 11
[Intelligent function module switch setting items]
Switch No.
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
POINT
(1) The settings made with the intelligent function module switches become
effective after power is switched OFF, then ON or the programmable controller
CPU is reset.
Setting change during operation is also not available.
(2) When the intelligent function module switch setting has not been made, the
initial values of each switch are used for operation.
REMARK
For the operation method of GX Developer, refer to the GX Developer Operating
Manual.
(1) Operation mode setting (Switch 1)
Set the operation mode of the QJ71MT91, such as the online or offline mode.
Set value
Item
0000
Online
H
0001
Offline
H
000D
Hardware test
H
000E
Self-loopback test
H
: A switch 1 error (error code: 7301
indicated in the table.
If the switch error has occurred, correct the switch setting and then switch the power OFF
and ON or reset the programmable controller CPU.
Description
Operation mode setting
Communication condition setting
IP address setting (high order)
IP address setting (low order)
No setting (blank)
Normal operation mode. Communicates with the target
device.
Disconnects the local station from the network.
In the offline mode, parameter setting cannot be executed.
Communication with the other station is not available,
either.
Tests the RAM and ROM of the QJ71MT91.
(Refer to Section 6.5.1)
Checks the hardware including the send/receive circuits of
the QJ71MT91. (Refer to Section 6.5.2.)
) will occur if the set value is other than the value
H
MELSEC-Q
Initial Value
Reference
(1) in this
0000
H
section
(2) in this
0000
H
section
C001
(3) in this
H
section
00FE
H
Description
6 - 11