I/O Signals For The Programmable Controller Cpu; List Of I/O Signals - Mitsubishi MELSEC-Q series User Manual

Gx configurator-da. channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.3

I/O Signals for the Programmable Controller CPU

3.3.1

List of I/O signals

Table 3.5 shows a list of the I/O signals for the Q66DA-G.
Signal direction
Q66DA-G
Device No
X0
X1
X2
X3
X4
X5
X6
X7
External power supply READY
X8
High resolution mode status flag
Operating condition setting
X9
XA
Offset/gain setting mode flag
XB
Channel change completed flag
XC
Set value change completed flag
XD
XE
Warning output signal
XF
Table3.5 List of I/O signal
CPU module
Signal name
Module READY
*1
Use prohibited
completed flag
*1
Use prohibited
Error flag
*1 These signals cannot be used by the user since they are used by the system.
If these are turned ON/OFF by the sequence program, the function of the
Q66DA-G cannot be guaranteed.
3.3 I/O Signals for the Programmable Controller CPU
Signal direction
CPU module
Device No.
Y0
Y1
CH1 Output enable/disable flag
Y2
CH2 Output enable/disable flag
Y3
CH3 Output enable/disable flag
Y4
CH4 Output enable/disable flag
Y5
CH5 Output enable/disable flag
Y6
CH6 Output enable/disable flag
Y7
Y8
Y9
Operating condition setting request
YA
User range writing request
YB
Channel change request
YC
Set value change request
YD
YE
Warning output clear request
YF
3.3.1 List of I/O signals
Q66DA-G
Signal name
*
1
Use prohibited
*1
Use prohibited
*1
Use prohibited
Error clear request
3
- 21
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q66da-g