Mitsubishi QJ71MT91 User Manual page 216

Modbus/tcp interface module melsec-q series
Hide thumbs Also See for QJ71MT91:
Table of Contents

Advertisement

10 DEDICATED INSTRUCTIONS
Type Specification of the Target MODBUS
Set
Read target
values
0100
Coil
H
0200
Input
H
0400
Input register
H
0500
Holding register
H
0700
Extended file register
H
0001
H
No specification
0005
H
0007
H
0505
Holding register
H
10 - 5
*4: Set "0" for the case of write only.
*5: Set "0" for the case of read only.
*6: The combinations of the read and write targets that can be set in the target
MODBUS
device type setting and the setting ranges of the access points are
R
as indicated in the following table.
Device
R
Write target
No specification
Coil
Holding register
Extended file register
Holding register
1)
No combination setting other than the above is allowed for the type
specification of the target MODBUS
2)
Simultaneous execution of read and write with a single instruction is
allowed only for 0505
3)
Read file record (FC: 20) and Write file record (FC: 21) allows access to
multiple areas in one communication, however, only one area is accessible
in one communication when using this dedicated instruction.
POINT
(1) When the close option setting of the execution type ((S1)+0) is "TCP connection is closed
after instruction completion", TCP connection is closed after the dedicated instruction
has been completed and the completion device (D2) has turned ON.
If the dedicated instruction is executed again for the same target device during this TCP
connection closing processing, it is completed with an error.
When the execution interval of the dedicated instruction for the same target device is
short, set the close option to "TCP connection is not closed after instruction completion".
(2) Specify "(device number) - 1" as the device number.
However, this does not apply to the file number and device number specified for the
Read/write file record.
(3) When access is made to the bit device (coil, input) of the slave, the fraction bit is handled
as described below.
[Read]
When the read access points are 35 points
<Read data storing device (D1)>
to
bF
D100
D101
D102
Remaining area is masked by 0.
[Write]
When the write access points are 5 points
<Write data storing device (S2)>
to
bF
D300
Remaining area is ignored.
Function Code
01
Read coils
02
Read discrete inputs
04
Read input registers
03
Read holding registers
20
Read file record
15
Write multiple coils
16
Write multiple registers
21
Write file record
23
Read/write multiple registers
device ((S1)+8).
R
(Read/Write Multiple Registers).
H
<Target slave device area>
b0
bF
Read
<Target slave device area>
Write
b0
bF
MELSEC-Q
Access Points Setting Range
Read points
Write point
1 to 2000
1 to 2000
1 to 125
1 to 125
1 to 124
1 to 1968
1 to 123
1 to 122
1 to 125
1 to 121
to
b0
116640 to 116625
116656 to 116641
116672 to 116657
to
b0
122544 to 122529
10 - 5