3.3 Power Supply Specifications

Item
Input power supply voltage
Fuse (built-in, not
exchangeable)
Power consumption
At backlight off
Inrush current
Permissible instantaneous
power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance
Grounding
Remark
Operation at momentary power failure
GT1020-LBD
24VDC (+10% -15%), ripple voltage 200mV or less
0.4A
1.9W (80mA/24VDC) or less
1.2W (50mA/24VDC) or less
13A or less (26.4VDC) 1ms
Within 5ms
Noise voltage : 1000Vp-p
Noise width
: 1 s (by noise simulator of 30 to 100Hz noise frequency)
500VAC for 1 minute
(across power supply terminals and earth)
10M
or larger by insulation resistance tester
(across power supply terminals and earth)
Class D grounding (100
To be connected to the panel when grounding is not
possible
The GOT continues to operate even upon 5ms or shorter instantaneous power
failure.
The GOT stops operating if there is extended power failure or voltage drop, while it
automatically resumes operation as soon as the power is restored.
WWW.NNC.IR
Specifications
GT1020-LBD2
or less),
3.3 Power Supply Specifications
GT1020-LBL
5VDC (±5%), supplied from
the PLC
1.1W (220mA/5VDC) or less
0.6W (120mA/5VDC) or less