Appendix 4: Regulatory Approvals
The CIE and notification equipment should be located and supervised to minimize the risk of vandalism or sabotage. It is preferable for the CIE,
signaling and network equipment to be located in an area where a confirmed activation will be generated.
HS2128, HS2064, HS2032, HS2016 are compliant with criteria for sequentially confirmed intruder alarm systems as per Standard BS8243:2010.
For an alarm condition to be regarded as sequentially confirmed:
a) The HS2128, HS2064, HS2032, HS2016 should be configured so that at least two separate alarm conditions are reported, each originating
from an independent detector within the confirmation time; Section [042] option 003 (Sequential Detection), section [005]>[000], Burglary
Verification Timer set to a value between 30 and 60.
b) The two detectors should either be of:
1) different technologies which are permitted to have overlapping areas of coverage; or
2) the same single technology and not have overlapping areas of coverage.
To be regarded as independent, each detector should be configured to report alarm conditions separately to the HS2128, HS2064, HS2032,
HS2016.
The HS2128, HS2064, HS2032, HS2016 are capable of supporting the completion of the full setting procedure by one of the following methods:
a) push button switch mounted outside the supervised premises. Instructions to be provided for the zone type to be programmed for the key
arming; or
b) protective switch (i.e., door contact) fitted to the final exit door of the alarmed premises or area. Use zone type 016 (Final Door Set) for the final
exit door.
In this case the setting procedure is a two-stage process of initiating the setting procedure within the supervised premises (e.g., using wireless key
PG8929,PG8939, PG8938, PG8949 or user code) followed by completion of setting by one of the two methods described above.
This prohibits the use of a timed exit procedure.
If a protective switch (i.e. door contact) is used as the method of completion of setting, then the keypad should be sited near to the final exit door so
that the IAS can be unset promptly. Where appropriate, additional internal audible indications (PG8911 indoor sirens) should be provided so that
persons within a building are informed that the HS2128, HS2064, HS2032, HS2016 are due to be set. Additional keypads should be provided,
where appropriate, so that if the alarm panel is set there are means available locally within the supervised premises to unset the system.
HS2128, HS2064, HS2032, HS2016 are capable of supporting the following unsetting methods in accordance with BS8243:
6.4.2 Prevention of entry to the supervised premises before the HS2128, HS2064, HS2032, HS2016 are unset. Unsetting using PG8929,PG8939,
PG8938, PG8949 wireless key before entering the supervised premises causes or permits the initial entry door to be unlocked. Program PGM1 or
PGM2 in Section [009] to activate when system is disarmed and release the mag-lock on the entry door.
Compliance labeling should be removed or adjusted if non-compliant configurations are selected.