Auxiliary Undervoltage - GE 850 Instruction Manual

Feeder protection system/feeder protection and control
Hide thumbs Also See for 850:
Table of Contents

Advertisement

PROTECTION
Auxiliary
Undervoltage
4–196
The 850 relay provides two identical Auxiliary Undervoltage (UV) elements per protection
group, or a total of 12 elements. Each Auxiliary Undervoltage element may be used to
protect voltage sensitive loads and system components against sustained undervoltage
conditions. This element may be used for permissive functions, initiation of the source
transfer schemes and similar functions.
The Auxiliary Undervoltage element may be set as an instantaneous element with no time
delay or as a time delayed element which can be programmed with definite time, inverse
time or FlexCurves. The Auxiliary Undervoltage element has a programmable minimum
operating threshold to prevent undesired operation when voltage is not available. The
input voltage is the auxiliary voltage.
The settings of this function are applied to auxiliary voltage input to produce Pickup and
Trip flags. The Auxiliary UV Pickup flag is asserted when the auxiliary input voltage is below
the PKP value. The Auxiliary UV Trip flag is asserted if the element stays picked up for the
time defined by Pickup time delay or for the time defined by the selected inverse curve/
FlexCurve. The element drops from Pickup without operation if the measured voltage rises
above 102 to 103% of the Pickup value before the time for operation is reached.
The minimum voltage setting selects the operating voltage below which the element is
blocked (a setting of "0" will allow a dead source to be considered a fault condition).
This element may be used to give a desired time-delay operating characteristic versus the
applied voltage, or as a definite time element. For the inverse time setpoint, the
undervoltage delay setpoint defines a family of curves as described in
Curves
on page 4-190.
Path:
Setpoints > Protection > Group 1(6) > Voltage Elements > Auxiliary UV 1(2)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS
Undervoltage