CHAPTER 4: SETPOINTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
BLOCK GROUND IOC 1
Range: Off, On
Default: Off
If set to "On," the operation of the GROUND IOC 1 protection element is be blocked after
the Cold Load Pickup condition is detected.
RAISE PHASE TOC 1/2 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the PHASE OVERCURRENT TOC 1/2
protection element by raising the Pickup level.
RAISE NEUTRAL TOC 1/2 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEUTRAL OVERCURRENT TOC 1/2
protection element by raising the Pickup level.
RAISE GROUND TOC 1 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the GROUND TOC 1 protection element by
raising the Pickup level.
RAISE SENS GND TOC 1 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the SENSITIVE GROUND TOC 1 protection
element by raising the Pickup level.
RAISE NEG SEQ TOC 1 PKP
Default: 0
Range: 0 to 100% in steps of 1%
The setpoint determines the characteristics of the NEGATIVE SEQUENCE TOC 1
protection element by raising the Pickup level.
SELECT SETTING GROUP
Range: Active, Group 1,2,3,4,5,6
Default: Active
The setpoint determines the setting group that is used after the Cold Load Pickup
condition is detected.
BLOCK
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
OUTPUT RELAY 3 (X)
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
CONTROL
4–319