Routing - GE 850 Instruction Manual

Feeder protection system/feeder protection and control
Hide thumbs Also See for 850:
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS

Routing

850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
When the configuration card is present, a default route and a maximum number of 6 static
routes can be configured. The default route is used as the last choice, if no other route
towards a given destination is found.
Figure 4-8: Device Display for Routing Hierarchy
SETTINGS
DEFAULT ROUTE:
Gateway Address
Range: Standard IPV4 unicast address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the gateway of the default route to be used by IP traffic sent from the
relay, if no other route towards a given IP destination is found.
This setting is available only if the communications card is present.
STATIC ROUTE 1 to 6:
Rt1 (2,3,4,5,6) Destination
Range: Standard IPV4 network address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the destination IPv4 route. This setting is available only if the
communications card is present.
Rt1 (2,3,4,5,6) Mask
Range: Standard IPV4 network mask format
Default: 255.0.0.0
This setting sets the IP mask associated with the route. This setting is available only if the
communications card is present.
Rt1 (2,3,4,5,6) Gateway
Range: Standard IPV4 unicast address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the destination IP route. This setting is available only if the
communications card is present.
ADDING AND DELETING STATIC ROUTES
Defaults:
Rule #1.
By default, the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This
is equivalent to saying that the static routes are not configured. When the destination
DEVICE
4–37