Usb - GE 850 Instruction Manual

Feeder protection system/feeder protection and control
Hide thumbs Also See for 850:
Table of Contents

Advertisement

DEVICE

USB

FASTPATH:
FASTPATH:
4–26
Quick Start Procedure
1.
The PC WiFi Network Settings are as follows:
Passphrase: provided with the 8-Series relay
2.
The Access Point Settings are given below:
IP address:
192.168.0.1
Subnet Mask:
255.255.255.0
SSID:
same as entered on the PC (SSID provided with the 8-Series relay)
Broadcast
disabled
Security type:
WPA2-PSK (WPA2-Personal)
Encryption:
AES
Passphrase:
same as entered on the PC (Passphrase provided with the 8-Series relay)
DHCP enabled
range of 192.168.0.2 to 192.168.0.11
3.
If the 8-Series relay(s) are in range, they automatically connect to the configured
Access Point.
4.
Start EnerVista on a PC and use the Discover function, all relays within range appear
and are populated in Enervista for initial configuration and commissioning.
5.
Once the relay is configured, change the 8-Series relay default WiFi SSID and
Passphrase settings before the relay goes into service.
Figure 4-7: Example of WiFi Deployment
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
again for proper communication to be established over USB.
Connecting multiple 8 Series relays over USB to a single PC is not possible because in the
case of USB, the IP address of the device 172.16.0.2 is constant.
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS