A1 STATUS

Clock

Contact inputs

Output relays

Output relays -
Breaker
4–6
PATH:
ACTUAL VALUES > A1 STATUS > CLOCK
CURRENT DATE
Feb 12 2009
Range: Date in format shown
Indicates today's date.
CURRENT TIME
09:17:12
Range: Time in format shown
Indicates the current time of day.
PATH:
ACTUAL VALUES > A1 STATUS > CONTACT INPUTS
52a (CI #1)
OFF
Range: Off, On
Shows the input status when connected to a 52a breaker auxiliary contact.
52b (CI #2)
OFF
Range: Off, On
Shows the breaker status when connected to a 52b breaker auxiliary contact.
CONTACT INPUT 3 to 10
OFF
Range: Off, On
Message displays the state of the contact input. The message "ON" indicates that the
contact input is energized, and message "OFF" indicates a de-energized contact.
PATH:
ACTUAL VALUES > A1 STATUS > OUTPUT RELAYS
Output Relay #1 (TRIP)
OFF
Range: Off, On
The "ON" state of Output Relay #1 (Breaker TRIP) shows that a TRIP command has been
sent to the breaker.
Output Relay #2 (CLOSE)
OFF
Range: Off, On
The "ON" state of Output Relay #2 (Breaker CLOSE) shows that a CLOSE command has
been sent to the breaker.
Output Relay #3 (START INHIBIT)
OFF
Range: Off, On
CHAPTER 4: ACTUAL VALUES
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL