CHAPTER 6: SETPOINTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
BF TIME DELAY 2 / WELDED TIME DELAY 2
Range: 0.00 to 1.00 s in steps of 0.01 s
Default: 0.00 s
This timer does not start until a trip command is recognized, timer BF / WELDED TIME
DELAY1 has expired, and at least one of the phase currents is above the setting BF /
WELDED CURRENT.
OUTPUT RELAY 4 to 6 / OUTPUT RELAY 5 to 6
Range: Do not operate, Operate
Default: Do not operate
Any assignable output relay can be selected to operate upon Breaker Failure / Welded
Contactor operation. When the SWITCHING DEVICE is selected as BREAKER, the
assignable output relays will be Output Relay 4 to 6. When the SWITCHING DEVICE is
selected as CONTACTOR, the assignable output relays will be Output Relay 5 to 6.
S4 CONTROL
6–143