GE 339 Instruction Manual page 26

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

MECHANICAL INSTALLATION
Φ
2–4
Figure 4: Mounting tabs (optional)
1.
From the front of the panel, slide the empty case into the cutout until the bottom tab
clicks into place (see above).
2.
From the rear of the panel screw the case into the panel at the 8 screw positions
shown above.
3.
If added security is required, bend the retaining "V"tabs outward, to about 90°. These
tabs are located on the sides of the case and appear as shown above.
The relay can now be inserted and can be panel wired.
Figure 5: Panel cutout dimensions
5.350" 0.010"
(135.9 mm 0.25mm)
4.100" 0.010"
(104.1 mm 0.25 mm)
0.200"
(5.1 mm)
"V" TABS
BOTTOM TAB
±
±
±
±
L
C
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION
6.900" 0.010"
(175.3 mm 0.25 mm)
6.000" 0.010"
±
L
(152.4 mm 0.25 mm)
±
C
4.000" 0.010"
±
(101.6 mm 0.25 mm)
±
±
±