Two-Speed Motor - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

S3 PROTECTION

Two-speed motor

A B C
6–116
Two-speed motors have two windings wound into one stator. These motors rely on
contactors to accomplish speed changes by altering the winding configurations. The 339
motor relay provides a complete set of protective functions for each speed.
The 339 motor relay provides proper protection for a two-speed motor where there are
two different full-load values. The 339 algorithm integrates the heating at each speed into
one thermal model using a common Thermal Capacity Used Register for both high and low
speeds.
In the figure below, contactor L and H are interlocked so that only one contactor can be
energized to select either low speed or high speed. This figure shows the AC connections
for a two-speed motor where CTs connected to low and high speed are paralleled, such
that the 339 relay can measure the motor current when the motor is running at either low
or high speed, and it will switch CT Primary and motor FLA settings as per the motor
running speed. This function is accomplished by detecting the input status from the motor
speed switches.
Figure 38: Two-speed motor connections
52
H
H
H
896LH.CDR
L
L
L
E5 D5 E6 D6 E7 D7
I
I
I
I
I
A
A
B
B
C
CURRE T I PUTS
52a
C1
52a (C1 #1)
C2
52b (C1 #2)
C3
L
H
C10
C11
COMMON
-
+
DC
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
T1
H
T2
H
T3
T4
T5
T6
I
C
339
Motor Protection System
MOTOR

Advertisement

Table of Contents
loading