Underfrequency - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

S3 PROTECTION

Underfrequency

6–96
The 339 provides 2 Underfrequency Protection elements. Each element can be set to either
cause a trip or generate an alarm when the frequency of the input voltage (wye-connected
VT: VAN; delta-connected VT: VAB) drops below the pickup level for a specified time delay. If
it is desirable to have an alarm before a trip occurs, the user can set the function of one
Underfrequency element to ALARM, and the function of another element to TRIP.
The Underfrequency element is blocked VAN is below the set MIN VOLTAGE. This setting
may be used to prevent nuisance alarms or trips when the bus is not energized. If a dead
source is desirable to be considered as a fault condition, set this setting to "0.00xVT".
This feature may be useful for load shedding applications on large motors. It could also be
used to load shed an entire feeder if the trip was assigned to an upstream breaker.
Underfrequency can also be used to detect loss of power to a synchronous motor. Due to
motor generation, sustained voltage may prevent quick detection of power loss. Therefore,
to quickly detect the loss of system power, the decaying frequency of the generated
voltage as the motor slows can be used.
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to Chapter 3 - Working with the Keypad.
PATH:
SETPOINTS > S3 PROTECTION > UNDER-FREQUENCY1(2)
UNDRFREQ 1(2) FUNC
Range: Disabled, Alarm, Latched Alarm, Trip
Default: Disabled
The selection of the Latched Alarm, Alarm, or Trip setting enables the Underfrequency
function. If the operating condition is satisfied when Trip is selected as the function, the
logic operand ANY TRIP OP will be asserted, which in turn will activate the "TRIP" LED and
operate the "Trip" output relay. If Alarm is selected, the "ALARM" LED will flash upon
Underfrequency operation, and will automatically reset when the activating condition
clears. If Latched Alarm is selected, the "ALARM" LED will flash upon Underfrequency
operation, and will stay "ON" after the condition clears, until a reset command is
initiated. The TRIP output relay will not operate if the Latched Alarm or Alarm function is
selected. Any assignable output relays can be selected to operate when the setting
UNDRFREQ FUNC is selected as Latched Alarm, Alarm, or Trip.
UNDERFREQ PKP
Range: 40.00 to 70.00 Hz in steps of 0.01 Hz
Default: 59.00 Hz
This setting defines the Underfrequency pickup level; it is usually set to a frequency level
considered dangerous for the stability of the system.
UNDRFREQ DELAY
Range: 0.1 to 600.0 sec in steps of 0.1 sec
Default: 2.0 s
This setting specifies the time delay before Underfrequency operation.
MIN VOLTAGE
Range: 0.00 to 1.25 x VT in steps of 0.01 x VT
Default: 0.70 x VT
The minimum operating voltage level is programmable to prevent undesired
Underfrequency operation before voltage VAN becomes available, such as on faults
cleared by downstream protection or fuses.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS