CHAPTER 6: SETPOINTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
OUTPUT RELAY 4 to 6 / OUTPUT RELAY 5 to 6
Range: Do not operate, Operate
Default: Do not operate
Any assignable output relay can be selected to operate upon Underfrequency operation.
When the SWITCHING DEVICE is selected as BREAKER, the assignable output relays will
be Output Relay 4 to 6. When the SWITCHING DEVICE is selected as CONTACTOR, the
assignable output relays will be Output Relay 5 to 6.
BLOCK 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Three blocking inputs are provided for the Underfrequency feature. When any of the
selected blocking inputs is on, the Underfrequency function is blocked. The available
selections for each block can be any Contact input, Virtual Input, Remote Input, or Logic
Element.
S3 PROTECTION
6–97