The MVS offers several special functions to ensure safe and simple installation and
configuration.
Comprehensive Simulations
The MVS offers software-based simulation functions to check all aspects of
operation, including starting and stopping, protection mechanisms and signal inputs
and outputs. The simulations are accessed via the Commissioning Menu.
Low Voltage Test Mode
The low voltage test mode lets commissioning staff check the soft starter's
electrical configuration safely, without requiring access to specialised medium
voltage equipment. The MVS can start and stop a small three-phase motor, testing
associated equipment such as contactors and relays.