Disassembly and Assembly In...
Reinstall in reverse order of this procedure and tighten
hardware in accordance with chapter 1.7 General Torque
Tightening Values. See Figure 7.2 and Figure 7.3.
7.3.4 Power Card
1
15
14
13
12
6
11
10
9
Figure 7.3 Power Card
1
Mounting screws (T20)
2
F901
3
MK901
4
MK902
5
MK106
6
Mounting standoffs (0.3 in [8
mm])
7
MK500
8
MK501
Table 7.3 Legend to Figure 7.3
1.
Remove the control card mounting plate in
accordance with chapter 7.3.2 Control Card and
Control Card Mounting Plate.
2.
Unplug the power card connectors:
•
MK101
•
MK103
•
MK501
•
MK502
MG94A222
Service Manual
2
3
4
5
1
6
7
8
9
MK502
10
MK103
11
MK101
12
MK104
13
MK100
14
MK102
15
Current scaling card
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
•
MK902
•
any additional customer-supplied wiring
at MK500 and MK106
3.
Remove the five power card mounting screws
(T20).
4.
Remove the two standoffs (0.3 in [8 mm]).
5.
Remove the power card from the three plastic
standoffs.
6.
Remove the current scaling card from the power
card by pushing in the retaining clips on the
standoffs. The scaling card controls signals
operating specifically with this adjustable
frequency drive and is not part of the
replacement power card.
NOTICE!
Keep this scaling card for future reinstallation of any
replacement power card.
Reinstall in reverse order of this procedure and tighten
hardware according to chapter 1.7 General Torque
Tightening Values. When installing the power card, ensure
that the insulator sheet is installed behind the power card.
See Figure 7.2
7.3.5 AC Input Bus Bars
See Figure 7.1 for location of bus bars.
7.3.5.1 Electrical Fuses Only
1.
Remove electrical fuses by removing six nuts (0.5
in [13 mm]), one at each end of each fuse.
2.
Remove three nuts (0.4 in [10 mm]) at the top of
of the bus bars. One per phase.
3.
Remove the bus bars.
Reinstall in reverse order of this procedure and tighten
hardware according to chapter 1.7 General Torque
Tightening Values.
7.3.5.2 RFI Only
1.
Remove three nuts (0.4 in [10 mm]) at the top of
the RFI filter, one per bus phase.
2.
Remove six nuts (0.5 in [13 mm]) at the bottom
of the RFI filter, two per phase.
3.
Remove four mounting screws (T20 thread-
cutting) connecting the RFI filter to the side
channels of the adjustable frequency drive.
7
7
93