Functional safety
8.7 PROFIsafe
Procedure
1. Select the "Master Reset" command in the "Device" menu.
The "Master Reset - ..." dialog opens.
2. Click the "Warm restart" button.
Note
Procedure when subsequently changing the F parameter
1. Carry out a change to an F parameter using HW Config or PDM.
2. Select the "Reset" command in the "Device" menu.
3. Click the "Warm restart" button.
8.7.8

Quit PROFIsafe commissioning

8.7.8.1

Preparations for maintenance and service

Procedure
Before you perform maintenance on a PROFIsafe device, proceed as follows:
1. Deactivate "PROFIsafe Commissioning".
2. Disable the write protection.
8.7.8.2

Deactivating PROFIsafe commissioning in SIMATIC PDM

Procedure
1. In the "Device" menu, select the "Wizard - PROFIsafe commissioning" command.
2. Click the "Change to unsafe mode" button.
3. Click the "Close" button.
8.7.8.3

Disable write protection using PIN in SIMATIC PDM

Procedure
1. In the "Device" menu, select the "Write protection" command.
2. Click on the "OFF" button.
3. Enter the user-defined PIN, the default PIN, or the super PIN.
160
The "Reset - ..." dialog opens.
As a result of the warm restart, the change to the F parameter is included in the cyclic
communication procedure.
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08