Example 1
You want to assign the input range 1 to 4 Pa to the output range 0 to 100%.
1. Set measurement type "Pressure".
2. Set the following parameters:
>
>
Note
The display can only show a part of the ASCII character set in both upper and lower case. If
you enter lower-case letters f, g, j, p, q, t, x, y, z in SIMATIC PDM in the parameter "Unit text
(output)", they will only be shown in upper case. The German letters ä, ö, ü, and ß, as well
as any ASCII characters with codes higher than 125, are displayed with a block symbol with
all segments on. Thus try to avoid language-specific characters.
Example 2
You want to convert the input range 0 to 400 m
instance, is 0 to 2000 barrels.
1. Set measurement type "Volume".
2. Set the following parameters:
>
>
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Pressure transducer block
Unit for measured value
(primary variable):
Analog input function block
Input starting value:
Input final value:
Output starting value:
Output final value:
Unit (output):
Pressure transducer block
Unit for measured value
(primary variable):
Analog input function block
Input for start-of-scale
value:
Input for final value:
Output for start-of-scale
value:
Output for final value:
Unit (output):
Unit text (output):
Operator control functions via PROFIBUS
Pa
1.0
4.0
0.0
100.0
%
to 200 l barrels. The output range, for
3
m
3
0.0
400.0
0.0
2000.0
Text
Barrels