Honeywell dcp100t Operator's Manual page 30

Digital controller programmer
Table of Contents

Advertisement

Message
Parameter
Process Low
Alarm 1 Value
Band Alarm 1
Value
Deviation
(High/Low)
Alarm 1 Value
Alarm 1
Hysteresis
Value
Process High
Alarm 2 Value
Process Low
Alarm 2 Value
Band Alarm 2
Value
9-4
Function
Display
If Alarm 1 is a Process Low
Alarm, the value of the
process variable at or
below which Alarm 1 will
become active (see
Figure 9-2).
If Alarm 1 is a Band
Alarm, the band of
process variable values
(centred on the setpoint)
outside which the
process variable will
cause this alarm to be
active.
If Alarm 1 is a Deviation
High/Low alarm, gives a
value above (positive
value) or below (negative
value) the setpoint. If the
process variable deviates
from the setpoint by a
margin greater than this
value, the alarm
becomes active (see
Figure 9-2).
Defines a hysteresis band
on the "safe" side of the
Alarm 1 value (see Figure
9-3).
If Alarm 2 is a Process
High Alarm, the value of
the process variable at or
above which Alarm 2 will
become active (see
Figure 9-2).
If Alarm 2 is a Process Low
Alarm, the value of the
process variable at or
below which Alarm 2 will
become active (see
Figure 9-2).
If Alarm 2 is a Band
Alarm, the band of
process variable values
(centred on the setpoint)
outside which the
process variable will
cause this alarm to be
active.
Available Settings/Values
(Lower Main Display)
Input Range Maximum to Input
Range Minimum.
Default = Input Range Minimum.
±(input span) from setpoint.
Default = 5 input units.
±(input range) from setpoint.
Default = 5 input range units.
1 LSD to 10% of input span (0 is an
invalid value).
Input Range Maximum to Input
Range Minimum.
Default = Input Range Maximum.
Input Range Maximum to Input
Range Minimum.
Default = Input Range Minimum.
±(input span) from setpoint.
Default = 5 input units.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents