Standard Operation Data - Mitsubishi PUMY-P60NKMU Technical & Service Manual

Split-type, heat pump air conditioners
Table of Contents

Advertisement

4-2. STANDARD OPERATION DATA (REFERENCE DATA)
Ambient
temperature
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor unit
Voltage
Compressor frequency
LEV opening
Indoor unit
Pressure
High pressure/Low pressure
Outdoor unit
Temp. of each
section
Indoor unit
OCH502C
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
kg [lbs-oz]
Discharge
Heat exchanger outlet
Accumulator inlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
26.7°C/19.4°C [80°F/67°F]
DB/WB
35°C/— [95°F/—]
Unit
m [ft]
A
21.4
V
Hz
45
Pulse
171 (P06)/426 (P24)
MPa [psi]
2.83/0.94 [411/136]
74 [165]
38 [100]
13 [55]
°C [°F]
14 [57]
74 [165]
27 [81]
10 [50]
12
Outdoor unit model
PUMY-P60NKMU(-BS)
21.1°C/— [70°F/—]
8.3°C/6.1°C [47°F/43°F]
4
4
06×2/24×2
5 [16-3/8]
2.5 [8-1/4]
15 [49-1/4]
Hi
8.5 [18]
27.4
230
56
215 (P06)/534 (P24)
2.93/0.66 [425/95]
68 [154]
3 [37]
0 [32]
−1 [30]
68 [154]
40 [104]
61 [142]