3. STANDARD OPERATION DATA

Model
Item
Capacity
SHF
Input
INDOOR UNIT MODEL
Power supply (V, phase, Hz)
Input
Fan current
OUTDOOR UNIT MODEL
Power supply (V, phase, Hz)
Input
Comp. current
Fan current
Condensing pressure
Suction pressure
Discharge temp.
Condensing temp.
Suction temp.
Ref. pipe length
Intake air temperature
Discharge air temperature
Fan speed (High)
Airflow (High)
Intake air temperature
Fan speed upper / lower
Airflow
PK18FL3
Unit
Cooling
Btu / h
18,500
0.82
kW
1.75
PK18FL3
115, 1, 60
kW
0.09
A
0.7
PU18EK
208/230, 1, 60
kW
1.66
A
12.0
A
0.75
psi-G
255
psi-G
82
˚F
171
˚F
118
˚F
51
ft
25
˚F
80
DB
˚F
67
WB
˚F
61
DB
˚F
59
WB
rpm
1,300
CFM
710
˚F
95
DB
˚F
75
WB
rpm
790
CFM
1,590
OC275-10
PK24FL3
Cooling
24,000
0.72
2.34
PK24FL3
115, 1, 60
0.09
0.7
PU24EK
1
1
208/230, 1, 60
2.25
11.5
0.65+0.65
240
74
155
114
44
25
80
67
58
56
1,300
710
95
75
750
750
3,170
PK30FL3
PK36FL3
Cooling
Cooling
30,000
34,200
0.75
0.71
3.06
3.47
PK30FL3
PK36FL3
115, 1, 60
115, 1, 60
0.12
0.12
1.0
1.0
PU30EK
PU36EK
1
208/230, 1, 60
208/230, 1, 60
2.94
3.35
14.0
17.5
0.65+0.65
0.75+0.75
247
247
77
73
163
163
116
116
46
43
25
25
80
80
67
67
59
58
58
56
1,380
1,380
990
990
95
95
75
75
750
760
750
3,170
3,350
1
760