7-3. SYSTEM CONTROL

Example for the System
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed
in the standard system with detailed explanation.
The explanation for the system in this section : Use 1 single outdoor unit and multiple outdoor units for M-NET remote control
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables
1. Standard operation
L
1
OC
51
TB3
TB7
M1 M2
S
M1 M2 S
• 1 remote controller for each
indoor unit.
• There is no need for setting
the 100 position on the remote
controller.
2. Operation using 2 remote controllers
OC
51
TB3
TB7
M1 M2 S
M1 M2 S
• Using 2 remote controllers
for each indoor unit.
3. Group operation
OC
51
TB3
TB7
M1 M2 S
M1 M2 S
• Multiple indoor units operated
together by 1 remote controller
Combinations of 1 through 3 above are possible.
OCH502C
system.
Use 1 single outdoor unit and multiple indoor units in the multiple outdoor
units for the M-NET remote control system.
L
2
IC
01
TB5
TB15
TB5
1 2
M1 M2 S
M1 M2 S
A B
A B
102
RC
101
IC
01
TB5
TB15
TB5
1 2
M1 M2 S
M1 M2 S
A B
A B
A B
101
151
102
152
RC
RC
RC
(Main)
(Sub)
(Main)
(Sub)
IC(Main)
IC(Sub)
01
02
TB5
TB15
TB5
TB15
1 2
1 2
M1 M2 S
M1 M2 S
A B
101
RC
21
Wiring Method and Address Setting
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit
(OC) to terminals M1 and M2 on the transmission
IC
cable block (TB5) of each indoor unit (IC). Use non-
02
polarized 2 wire.
b. Connect terminals M1 and M2 on transmission cable
TB15
terminal block (TB5) for each indoor unit with the
1 2
terminal block (TB6) for the remote controller (RC).
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (RC)
a. Same as above.
b. Same as above.
IC
c. Set address switch (on outdoor unit P.C.B) as
shown below.
02
Unit
TB15
Indoor Unit (IC)
1 2
Outdoor unit
(OC)
Main Remote
Controller (RC)
A B
Sub Remote
Controller (RC)
RC
a. Same as above.
b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most
recent address within the same indoor unit (IC) group
to terminal block (TB6) on the remote controller.
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
IC (Main)
001 to 050
IC (Sub)
001 to 050
Outdoor Unit
051 to 100
Main Remote
101 to 150
Controller
Sub Remote
151 to 200
Controller
d. Use the indoor unit (IC) within the group with the
most functions as the IC (Main) unit.
Setting Method
Range
001 to 050
Use the smallest
address of all the indoor
051 to 100
unit plus 50.
Indoor unit address plus
101 to 150
100.
Range
Setting Method
001 to 050
Use the smallest
051 to 100
address of all the indoor
units plus 50.
Indoor unit address plus
101 to 150
100.
Indoor unit address plus
151 to 200
150.
Range
Setting Method
Use the smallest address within the
same group of indoor units.
Use an address, other than that of
the IC (Main) from among the units
within the same group of indoor
units. This must be in sequence with
the IC (Main).
Use the smallest address of all the
indoor units plus 50.
Set at an IC (Main) address within
the same group plus 100.
Set at an IC (Main) address within
the same group plus 150.