Interpret Controller LEDs

RUN Indicator
Color
Description
off
The controller is in Program or Test
mode.
solid green
The controller is in Run mode.
I/O Indicator
Color
Description
off
Either:
• There are no devices in the I/O
configuration of the controller.
• The controller does not contain a
project (controller memory is empty).
solid green
The controller is communicating with
all the devices in its I/O configuration.
flashing
One or more devices in the I/O
green
configuration of the controller are not
responding.
flashing red
The chassis is bad.
ControlLogix® Controller and Memory Board 33
Publication
1756-IN101J-EN-P - November 2004
Recommended Action
See "Choose the Operating
Mode of the Controller" on
page 39.
Recommended Action
• Add the required devices to
the I/O configuration of the
controller.
• Download the project to the
controller.
None
Go online with RSLogix 5000
software and check the I/O
configuration of the controller.
Replace the chassis.