Clear a Major Fault

1. Go online with RSLogix 5000 software and get the fault code.
2. Determine what to do next:
Fault Type Fault Code
1
60
1
61
none of the
none of the
above
above
To use the keyswitch of the controller to clear a major fault, turn the keyswitch in the
following sequence:
1. PROG
2. RUN
3. PROG
ControlLogix® Controller and Memory Board 37
Action
A. Clear the fault.
B. Download the project to the controller.
C. Return the controller to the run/remote run mode.
If the problem persists:
A. Before you cycle power to the controller, record the state
of the OK and RS232 LEDs.
B. Contact Rockwell Automation support. See the back of this
publication.
A. To get diagnostic information about the fault, see
Knowledgebase document A92558072. To get the
document, see the back of this publication.
B. Clear the fault.
C. Download the project to the controller.
D. Return the controller to the run/remote run mode.
A. Clear the fault.
B. Correct the reason for the fault.
C. Return the controller to the run/remote run mode.